Island Breeze Technician Certification Program

Component Bench, ID and Test (Demo)

Module F8 Demo transcript Duration 10 minutes 30 seconds

INTRO (0:00 to 0:30)

ON CAMERA, Darrel at the bench, components laid out in a row

Everything on this bench came off a real system, and every one of them can strand a family in a hot house. In the next ten minutes I am going to pick up each part, tell you what it does in one sentence, and then prove it good or bad with a meter, the same tests you will do on the practical for this module. No guessing, no part swapping. The meter decides. Power is off and verified dead before my hands touch anything, every time.

MAIN (0:30 to 10:00)

Beat 1: Transformer (0:30 to 1:45)

ON-SCREEN: TRANSFORMER. PRIMARY = LINE SIDE. SECONDARY = 24V SIDE. 40VA

This is the transformer, the part that turns 240 volts into 24. Primary side, these heavier leads with the voltage taps; secondary side, the two 24 volt wires. This one is multi-tap, see the 208 and 240 labels, and the tap has to match the supply or your control voltage runs high or low.

OVERHEAD: meter on ohms, probes on primary leads

Dead test first, power off. Primary winding: I read 14 ohms, that is an intact winding. Secondary: under 1 ohm, also intact. OL on either side means an open winding and the part is done.

OVERHEAD: bench supply energized, meter on AC volts across secondary

Now live, with the primary fed. Secondary reads 26.8 volts. Is that a problem? No. A healthy 24 volt transformer reads anywhere from 24 to 29.5. Do not condemn a transformer for reading 27. The failure you condemn is line voltage at the primary and zero at the secondary. And before you ever replace one, check the control fuse and find out what blew it, or the new transformer dies the same death.

Beat 2: Relay (1:45 to 3:00)

ON-SCREEN: RELAY. COIL = 24V. CONTACTS = LINE VOLTAGE. NO + NC

General purpose relay. Two halves that never touch electrically: a 24 volt coil, and contact sets that carry line voltage. The diagram is printed right on the case: terminals one to three are normally closed, one to two are normally open.

OVERHEAD: ohmmeter on coil terminals

Coil first: 16 ohms. Intact. Now the contacts at rest: one to three, continuity, that is the normally closed set doing its job. One to two, OL, normally open, also correct.

OVERHEAD: 24V bench supply clipped to coil, audible click, meter re-tests both pairs

Now I energize the coil with 24 volts. Hear the click? The click is not proof. The meter is proof. One to two now shows continuity, one to three is open. Every set flipped. This relay passes. If the coil gets its 24 volts and a contact set refuses to move, the relay has failed. If the coil never gets 24 volts, the relay is innocent, your problem is upstream.

Beat 3: Contactor, good and bad (3:00 to 4:45)

ON-SCREEN: CONTACTOR = HEAVY DUTY RELAY. COIL 24V. L1 L2 IN, T1 T2 OUT

The contactor is the relay's big brother, built to switch compressor current. Line lugs L1 and L2 on top, load lugs T1 and T2 below, 24 volt coil terminals on the side, and the contacts ride this spring loaded bar.

OVERHEAD: closeup of new contactor contacts, then the burned one

Here is a new one: bright silver contact faces. Here is one I pulled off a system: pitted, black, and there is a dead earwig pressed into the contact face, which in Phoenix is a whole genre of no-cool call. Never file these. The silver coating is the contact, file it off and the part is scrap.

OVERHEAD: ohmmeter, coil test, then static contact test with bar pressed down

Tests. Coil: 11 ohms, intact. Static contact test, power off, wires off: I press the bar down and read L1 to T1. The new one: 0.3 ohms. Pass. The burned one: 6 ohms. That is a fail, anything over 1 ohm is a fail, those contacts have become a heater.

ON-SCREEN: UNDER LOAD: 2V DROP OK. OVER 5V = REPLACE

In the field there is a third test, with the unit running: voltage drop across each closed contact. Two volts or less, fine. More than five, the contactor is burning your customer's power as heat, replace it.

Beat 4: Dual run capacitor, the 21 percent part (4:45 to 7:00)

ON-SCREEN: CAPACITORS = 21 PERCENT OF AC SERVICE CALLS

Now the most important part on this bench. One instructor logged 242 air conditioning calls and 52 of them, about 21 percent, were this part. The dual run capacitor: two capacitors in one can, one for the compressor, one for the condenser fan.

OVERHEAD: closeup of terminal markings C, HERM, FAN

Three terminals and the markings matter. C, common, gets power from the load side of the contactor. HERM, hermetic, goes to the compressor start winding, that is the big number, 45 microfarads on this one. FAN goes to the condenser fan motor, the small number, 5. Swap HERM and FAN and the compressor gets 5 microfarads instead of 45, and it will hum, overheat, and trip. Photograph the wiring before you pull a single wire.

OVERHEAD: bleed resistor tool across terminals, then meter on capacitance mode

Safety first: a capacitor stores charge after power is off. I discharge it through a bleed resistor, never my fingers. Wires off, because testing in circuit reads the motor windings too and the number is fiction. Meter on capacitance mode. C to HERM: 44.1 microfarads against a 45 rating, that is inside 6 percent, pass. C to FAN: 4.9 against 5, pass.

OVERHEAD: the failed flat-top capacitor, meter reads low

Now the one I pulled off a real no-cool. Look at it: flat top, clean, looks brand new. C to HERM: 31 microfarads against 45. That is 31 percent low. Stone dead, and it looked perfect. The bulged one over here, you do not even need the meter, a domed top is an automatic replace. But the lesson is the flat one: looks prove nothing, the meter decides. The rule: more than 6 percent below rating, replace it.

ON-SCREEN: RULE: REPLACE BEYOND MINUS 6 PERCENT OF RATING. ASK WHY IT DIED.

And one habit before we move on. This capacitor died of something: heat, a dirty coil, a tired motor, a storm surge. When you replace one, your last step is an amp reading on the motor it serves, against the nameplate. High amps means the motor killed this capacitor and will kill the next one. The full root cause method is module D23. The habit starts now.

Beat 5: PSC motor vs ECM (7:00 to 9:00)

ON-SCREEN: PSC = WINDINGS + RUN CAP. ECM = MOTOR + ELECTRONIC MODULE

Two motors, two generations. This PSC condenser fan motor is the old workhorse: two windings sharing a common terminal, and it cannot run without its capacitor.

OVERHEAD: ohmmeter walks the three terminal pairs

ID the windings by resistance: common to run, lowest, I read 4 ohms. Common to start, higher, 17 ohms. Start to run, the sum, 21. That pattern, low, high, sum, is how you confirm windings on any PSC motor, and OL on any pair means an open winding. Last check, any winding to the metal case: OL. Continuity to the case means a grounded motor, replace it. And remember the classic: a PSC that hums and then runs when you spin the blade is telling you its capacitor is dead.

OVERHEAD: ECM blower, module end cap shown

This is an ECM, electronically commutated motor. No capacitor anywhere. The module on the back converts the power and fires the windings electronically. Constant torque versions take 24 volt taps; constant airflow versions take data from the board and hold a target airflow no matter what the duct does. Here is the trap: this module is the expensive half, and techs condemn it daily when the real fault is an input. Before you ever blame the module: line voltage at the motor, command signal present, and spin the wheel by hand with power off. Dead input or seized bearing first, module last.

Beat 6: Sequencer (9:00 to 10:00)

ON-SCREEN: SEQUENCER = TIMED SWITCH. 24V HEATER + BIMETAL DISC. NOT A RELAY

Last part, the sequencer, from electric heat. It is a switch, but not a magnetic one. A little 24 volt heater inside warms a bimetal disc, and the disc snaps these M contacts closed, slowly, on purpose, so heat strips stage on one at a time instead of slamming the panel.

OVERHEAD: ohm the heater, then 24V applied, stopwatch graphic, contacts close after delay

Test: ohm the heater terminals, I read intact. Continuity across M, open at rest, correct. Now 24 volts on the heater and we wait. Watch the clock. There: about 40 seconds, M closes. Power off, and it takes its time reopening too, which is the feature, the blower keeps moving air until the elements cool. No closure after a minute with a good heater, the sequencer is done.

OUTRO (10:00 to 10:30)

ON CAMERA

Six parts, and every one proven with a meter, not a guess. That is the whole discipline of this trade in miniature. Your practical is exactly what you just watched: you will identify ten components cold, then test a transformer, a relay, a contactor, and a capacitor in front of me, and tell me pass or fail and why. Watch this video twice, then come take the bench.