Island Breeze Technician Certification Program

The IAQ and Zoning Walk, With Numbers

Module A36 Demo transcript Duration 11 minutes

INTRO (0:00 to 0:30)

Darrel at the front door, tool bag over the shoulder: This house has everything this module talks about. A media filter cabinet that has not been opened in over a year, a UV light somebody installed and forgot, flex duct in a Phoenix attic, and a two-zone system with an old-school bypass damper. The complaint is the upstairs never keeps up. We are going to survey all of it the only way that means anything: with a manometer and a notebook. Before and after, every change. No selling, just measuring.

ON-SCREEN: A36 Field Demo: one home, every IAQ claim checked by number

MAIN (0:30 to 10:45)

Beat 1: Baseline before anything (0:30 to 1:45)

Darrel sets the system cooling, both zones calling, and waits out the wet-coil runtime while narrating the C12 rule: fifteen minutes so the coil is wet and the numbers are honest. Manometer into the existing ports, close-up on the screens: return minus 0.49, supply plus 0.37. Tablet math on camera: TESP 0.86 against a 0.5 rating. Fan table overhead shot, finger trace at the verified speed tap: 1,240 CFM at 0.5, 985 at 0.8, 860 at 0.9. Interpolate at 0.86: call it about 910 CFM. Divide by 3 tons: about 303 CFM per ton. Darrel to camera: below the 350 floor. This system is strangled, and we have not opened a single panel yet. The split says return-heavy, 0.49 of 0.86, and the biggest thing on the return side of this house is that media cabinet.

ON-SCREEN: Return minus 0.49. Supply plus 0.37. TESP = 0.86 in WC, rated 0.5

ON-SCREEN: Fan table: about 910 CFM. 910 / 3 tons = 303 per ton. Below the 350 floor

Beat 2: The filter swap, with before and after (1:45 to 3:30)

Darrel opens the media cabinet and pulls the filter: a 4 inch MERV 13, fourteen months old, gray and heavy. He holds it next to the fresh one for the camera, then makes the teaching point while swapping: this is the right filter in the right cabinet, deep pleats, huge surface area, MERV 13 capture at a pressure the blower can afford when it is clean. The failure here was not the product, it was the calendar, and Phoenix dust sets the calendar. Monsoon season can load a filter in weeks. New filter seated, arrow toward the blower, cabinet closed. Back to the manometer, system running: return minus 0.31, supply plus 0.37. TESP 0.68. Fan table again: about 1,105 CFM, about 368 per ton. Darrel writes both number sets on the tablet, big enough for the lens: 0.86 before, 0.68 after, 303 per ton to 368 per ton. One filter, sixty-five points of static, and the system is back inside the window. That is the IB standard: a static reading before and after every filtration change, both numbers on the work order. Without the before number, the after number is just a number.

ON-SCREEN: BEFORE: 0.86 in WC, 303 CFM per ton. AFTER: 0.68 in WC, 368 CFM per ton

ON-SCREEN: IB STANDARD: static before AND after every filtration change

Beat 3: The UV light, serviced safely (3:30 to 5:00)

Darrel kills power at the service switch and narrates why before touching the coil compartment: UVC burns your corneas and you will not feel it until tonight, so the lamp goes dark before any panel opens, and you never look at a lit bulb. Panel off, second camera on the lamp: a coil-mounted UV lamp aimed across the evaporator face. Darrel gives the honest evidence in one breath: pointed at a wet, stationary coil, this thing earns its keep, continuous dose, keeps biofilm from matting the fins, protects the coil pressure drop we just paid to recover. The same bulb sold as an air purifier in the duct is a different story: the air crosses it in a fraction of a second and one bulb cannot dose moving air. Then the inspection: no date label on the bulb. Darrel holds the bulb up: this could be five years old. It still glows, but output decays long before the glow quits, so an undated bulb is an expired bulb. He checks what the lamp shines on, points out a chalky patch on a wire loom in the beam path for the camera, repositions the loom out of the beam, fits the replacement bulb, dates it with a marker, panel on, power on.

ON-SCREEN: Power OFF before the panel. Never look at a lit UVC bulb

ON-SCREEN: Coil UV: decent evidence. Duct-mounted single bulb: dwell time says no

ON-SCREEN: No date on the bulb = expired. Replace yearly, write the date on it

Beat 4: The attic duct walk (5:00 to 7:00)

Headlamp on, up the hatch, second camera following. Darrel narrates the stakes from the top of the ladder: typical duct systems leak 20 to 30 percent of the air the homeowner pays for, and this attic was 150 degrees an hour ago. Supply leaks dump cold air into the oven. Return leaks are worse, they suck this attic, dust and all, into the airstream ahead of that coil we just cleaned up. The finds, shot in sequence as he crawls: first, a supply collar where cloth duct tape has cooked to paper, peeling off in his hand, with dust streaking on the insulation below it, the leak's signature. Second, a takeoff joint with old mastic still solid: he raps it with a knuckle, this is what right looks like, brushed on decades ago and still sealed. Third, a panned return joint with a visible gap and blackened insulation around it: that black is filtered attic dust, this return has been eating attic air for years. Show-and-tell at the hatch: the mastic bucket and the UL 181 foil tape roll next to the dead cloth tape. The rules: mastic everywhere you can reach, UL 181 listed tape where you cannot brush, cloth duct tape never, and for the leaks buried where no hand goes, aerosol sealing injects sticky polymer from inside and seals gaps up to about five-eighths of an inch, with a leakage number printed before and after. Darrel closes the beat with the D25 recall, pointing at the gapped return joint: leaks are pressure relief. Seal this system tight and the static reading downstairs will likely come UP a little while the registers deliver MORE air. That is not a problem you caused, that is the duct system finally telling the truth. You re-measure after sealing, same as after a filter.

ON-SCREEN: Typical duct leakage: 20 to 30 percent of conditioned air

ON-SCREEN: Mastic = standard. UL 181 foil tape = legit. Cloth duct tape = banned

ON-SCREEN: Sealed ducts can read HIGHER static while delivering MORE air. Re-measure

Beat 5: The zone panel and damper exercise (7:00 to 9:15)

Back downstairs at the furnace. Darrel opens the zone panel cover, camera close on the board: two zones, zone 1 downstairs, zone 2 upstairs, one damper motor each, and up in the supply, a barometric bypass, a weighted arm on a damper connecting supply back to return. The exercise, narrated step by step so a camera operator can follow: manometer stays in the ports, system cooling. State one, both zones calling: TESP 0.68, the number from Beat 2. State two, Darrel forces zone 2 closed at the panel and the second camera catches the upstairs damper actuator driving shut: TESP climbs to 0.91. He talks over the climbing number: half the duct system just disappeared and this PSC blower is shoving the same effort against the half that is left. The bypass arm is supposed to swing open and relieve this, and it barely moved, the weight is set wrong. He adjusts the weight, the arm swings, static settles to 0.78. Then the honest verdict, delivered at the return: now feel this return air, it is cold, because that bypass is dumping 55 degree supply air straight back in. Every pass makes the coil's entering air colder, suction falls, and on a long one-zone afternoon this coil can ice. Field tests put the waste of an open bypass at 20 to 30 percent. This damper is not a solution, it is a confession. The real fix, and he says it plainly: modulating equipment with a communicating panel ramps the blower and compressor DOWN when one zone calls, so there is no excess air to dump. On this single-stage system today, we set the bypass correctly, we verify both dampers actually drive open and closed from the panel, and we write the static table on the work order: 0.68 both zones, 0.78 one zone with bypass working. The mis-wire check closes the beat: zone 1 call, hand on a downstairs register, air arrives where the call came from. Thirty seconds, and it has caught swapped zones more than once.

ON-SCREEN: Both zones: 0.68. Zone 2 closed, bypass stuck: 0.91. Bypass corrected: 0.78

ON-SCREEN: Bypass air does no work: 55 F air recirculated, coil runs colder every pass

ON-SCREEN: Modern answer: modulate the equipment down. Do not dump the excess

Beat 6: The write-up (9:15 to 10:45)

Darrel at the tablet, building the job record on camera, every line a number: filter swap with before and after statics, 0.86 to 0.68, CFM 303 to 368 per ton. UV bulb replaced and dated, beam path cleared, coil application noted as legitimate. Attic findings photographed: failed cloth tape collar, gapped return joint, sealing scope flagged with the 20 to 30 percent leakage context and a note that post-sealing static must be re-measured. Zone exercise table: 0.68 both zones, 0.91 as found one zone, 0.78 after bypass adjustment, both dampers verified driving, zones verified not swapped. He closes to camera: notice what we did not do today. We did not sell a box. Every recommendation in this record is a measurement somebody else can check, and the next tech who opens this history knows exactly what this system was doing on this date. That is what IAQ work looks like when a manometer runs the conversation.

ON-SCREEN: Every line of the write-up is a number with a before and an after

OUTRO (10:45 to 11:00)

Darrel at the truck: One house, four systems' worth of lessons, and not one guess. Filter by the numbers, UV by the evidence, ducts by the leak signatures, zones by the static table. Run the quiz, and when a customer asks you about anything on the IAQ shelf, answer the way we worked today: here is what it does, here is the evidence, here is what it costs your blower.

ON-SCREEN: A36 quiz next. What does it do? What is the evidence? What does it cost in static?