Island Breeze Technician Certification Program

Refrigerants and the PT Chart

Module F5 Foundations Prereq F4 In-person practical

Videos

Theory video
Theory video
Saturation and the PT Chart (Theory)
Video coming soon
Saturation and the PT Chart (Theory) Read the transcript
Demo video
Demo video
PT Chart Drills with a Gauge Set and a Bottle (Demo)
Video coming soon
PT Chart Drills with a Gauge Set and a Bottle (Demo) Read the transcript
Already know this material?

Take the 10-question test-out. Score 80 percent or better and this module is marked complete. One attempt only; if you miss, study the module and take the regular quiz.

The scene. It is your second week riding along. Your lead tech hooks a gauge set to a condenser on a 105 degree afternoon, glances at the low side gauge for two seconds, and says "evap coil is running about 52, that is a little high, let's check the filter before we even think about charge." He never touched a chart, never opened an app. He read a pressure and his brain instantly translated it into a temperature. That translation is the single most used mental skill in this trade, and this module installs it in your head. By the end of F5 you will look at 130 psig on an R-410A gauge and think "45 degrees" without effort.

Short Version

Every refrigerant has a fixed relationship between its pressure and the temperature where it boils or condenses. That relationship is printed on a pressure-temperature chart, called a PT chart. When liquid and vapor refrigerant exist together, the refrigerant is "saturated," and the PT chart tells you its exact temperature from its pressure, or its exact pressure from its temperature. Your gauges measure pressure; the PT chart converts that to saturation temperature, which is what your diagnosis actually runs on. R-410A is the refrigerant in most systems you will touch, R-454B and R-32 are the new mildly flammable replacements, and they all use POE oil that absorbs moisture from open air. Learn the chart, identify the refrigerant before you connect anything, and never trust cylinder paint color.

Key Values

R-410A PT mini-table (memorize these anchors)

Saturation values, pressure in psig (pounds per square inch gauge). The first three are the temperatures you care about on the suction side. The last four are the temperatures you care about on the head pressure side.

Saturation temperature (F)R-410A pressure (psig)Where you see it
40118Coil running cold, low end of normal cooling
45130Classic healthy evaporator coil target
50142Coil running warm, or a mild-load day
95296Condensing temp on a mild day
105340Condensing temp on a warm day
115390Condensing temp on a hot Phoenix day
125445Condensing temp in extreme heat or with a struggling condenser

GWP and safety class comparison

GWP means global warming potential: how much heat one pound of the gas traps in the atmosphere compared to one pound of carbon dioxide over 100 years. Safety classes come from ASHRAE Standard 34: the letter is toxicity (A means lower toxicity), the number is flammability (1 means no flame propagation, 2L means lower flammability with very slow burning velocity, 3 means highly flammable).

RefrigerantTypeGWPASHRAE safety classGlide
R-410AHFC blend (50% R-32, 50% R-125)1924A1 (non-flammable)Negligible (near-azeotropic)
R-32Single HFC675A2L (mildly flammable)None (pure fluid)
R-454BHFC/HFO blend (68.9% R-32, 31.1% R-1234yf)466A2L (mildly flammable)About 1.5 F

Note on GWP numbers: you will also see R-410A listed at 2,088. Both are published values from different IPCC assessment reports. Either way the story is the same: R-410A traps roughly four times the heat of R-454B, which is why it is being phased down.

Glide note for R-454B: glide means the refrigerant boils and condenses across a small temperature range instead of at one exact temperature, because its two ingredients have different boiling points. R-454B glides about 1.5 F. That is small enough that service practice feels like R-410A, but it is why R-454B charts show two columns (bubble point and dew point) and why blends with glide are charged as liquid.

Field Checklist: Reading Saturation Off a Gauge Set Correctly

  • Identify the refrigerant from the equipment nameplate before connecting anything. Never assume.
  • Analog (dial) gauges: the outer ring is pressure in psig. The inner colored rings are saturation temperature scales, one ring per refrigerant, each labeled (for example R-22, R-404A, R-410A). Find the ring labeled R-410A and read temperature where the needle crosses THAT ring. Reading the wrong ring gives you a wrong temperature with total confidence.
  • Digital manifold or wireless probes: select the refrigerant in the menu first. The device computes saturation temperature for whatever refrigerant is selected. If the menu says R-22 and the system holds R-410A, every displayed saturation temperature is garbage.
  • Low side (blue, compound gauge that reads pressure and vacuum) connects to the suction line service port. High side (red) connects to the liquid line service port.
  • Read pressure, convert to saturation temperature, and say it out loud as a temperature: "130 psig, that is a 45 degree coil." Train the habit now.
  • Cross-check against a paper PT chart or a refrigerant slider app until your anchors are memorized.
IB STANDARD
Island Breeze trucks stock R-410A for service work on the existing installed base, and R-454B for new RunTru and Goodman and Daikin equipment (Daikin and Goodman platforms also bring R-32 into the mix). Before any refrigerant is added to any system, the tech must positively identify the refrigerant from the nameplate and match it to the cylinder label. Identification before topping off is mandatory, no exceptions, and every charge event gets logged in ServiceTitan with date, system, refrigerant type, and pounds added.

Full Breakdown

What a refrigerant is, and what makes a good one

A refrigerant is a fluid chosen because it boils and condenses at useful temperatures under pressures we can build equipment to handle. In F4 you learned the cycle: the heat absorber (evaporator) boils liquid refrigerant to soak up heat indoors, and the heat rejector (condenser) condenses vapor back to liquid to dump heat outdoors. The refrigerant is the truck that hauls the heat.

Water technically works as a refrigerant. So does propane. So would dozens of fluids. What separates a good refrigerant from a science experiment:

  1. Useful boiling point. It must boil well below the temperatures we want to cool, at pressures above atmospheric. R-410A boils at roughly minus 52 F at atmospheric pressure. That means even the "low" side of an air conditioner runs at positive pressure, so a small leak pushes refrigerant out instead of sucking air and moisture in.
  2. Manageable pressures. The pressures at condensing temperatures must be something copper tubing, compressors, and hoses can contain. R-410A pushes this boundary: its critical pressure is about 696 psig, which is why every R-410A tool carries a higher pressure rating than the old R-22 era gear.
  3. High latent heat. Latent heat (from F3) is the heat absorbed or released during a state change. More latent heat per pound means less refrigerant has to circulate to move the same BTUs.
  4. Chemical stability and compatibility. It cannot attack the compressor oil, the motor windings, the copper, or the rubber seals.
  5. Safety. Low toxicity, low flammability. This is the A1 versus A2L versus A3 story covered below.
  6. Environmental footprint. No ozone destruction, and the lowest practical GWP. This requirement is new in historical terms and it is the reason the refrigerant in the box keeps changing.

No fluid wins all six. Every refrigerant in history is a compromise, and the history section below shows how the compromise keeps shifting.

Saturation: the core concept of this entire trade

Here is the idea everything else in refrigeration hangs on.

At any given pressure, a refrigerant has exactly one temperature where liquid and vapor can exist together. That temperature is the saturation temperature for that pressure. At that point the refrigerant is boiling (if heat is going in) or condensing (if heat is going out), and while it changes state, its temperature does not move. All the energy goes into the state change. That is latent heat at work, exactly as you saw with boiling water in F3.

Raise the pressure and the saturation temperature rises. Lower the pressure and it falls. Water does this too: at sea level water boils at 212 F, on a mountain it boils cooler, and in a pressure cooker it boils hotter. Refrigerant obeys the same law, just at temperatures useful for air conditioning.

Now restate the three conditions you met in F4, because saturation is the reference point for all of them:

  • Saturated: liquid and vapor together, sitting exactly at the saturation temperature for the current pressure. Inside most of the evaporator and most of the condenser, the refrigerant is saturated. A resting cylinder with liquid in it is saturated too, which is why a bottle is the perfect practice tool.
  • Superheated: vapor only, heated ABOVE saturation temperature. Superheat is the number of degrees above. If saturation is 45 F and the suction line measures 55 F, the vapor carries 10 degrees of superheat. Superheat proves there is no liquid left.
  • Subcooled: liquid only, cooled BELOW saturation temperature. If saturation at the condenser is 115 F and the liquid line measures 105 F, the liquid carries 10 degrees of subcooling. Subcooling proves there is no vapor left.

Why a technician cares: your gauges cannot see inside the coil, but they read pressure, and pressure tells you saturation temperature exactly. Compare saturation temperature to an actual line temperature from a clamp thermometer and you know precisely where the refrigerant stands. That comparison IS superheat and subcooling, and F6 is devoted to it. F5's job is to make the pressure-to-temperature translation automatic.

PT chart fluency: reading it both directions

A PT chart is a table with two columns: temperature and pressure. One column in, the other column out. You must be fluent in both directions, because the field demands both.

Direction one: pressure to temperature. This is the everyday direction. Your gauge reads 130 psig on an R-410A system. The chart says 130 psig sits at 45 F. You now know the evaporator coil is boiling refrigerant at 45 F. The gauge gave you a pressure; the chart turned it into the temperature your diagnosis runs on.

Direction two: temperature to pressure. This is the prediction direction. It is 95 F outside and a healthy condenser typically condenses about 20 to 25 degrees above outdoor air, so you expect a condensing temperature near 115 to 120 F. The chart says 115 F is 390 psig. Before you ever connect, you already know roughly what the high side gauge should read. If it reads 480, something is wrong and you knew it within seconds. Direction two is also how you verify a cylinder: a resting R-410A cylinder at 75 F should sit near its 75 F saturation pressure. If it reads well above chart pressure, the cylinder contains air or other non-condensable gas, or the wrong refrigerant.

Your gauges have the PT chart built in. That is what the inner temperature rings on an analog gauge are: a PT chart wrapped into a circle, one ring per refrigerant. A digital manifold is a PT chart in software: it measures pressure and displays saturation temperature for the refrigerant you selected. The numbers in both trace back to laboratory property data published by NIST, the National Institute of Standards and Technology, whose REFPROP database is the source nearly every chart, gauge ring, and slider app is computed from. The tools are fast, but the tech who also knows the anchors by memory (40 is 118, 45 is 130, 115 is 390) catches the wrong-ring and wrong-menu mistakes that fool everyone else.

One more definition pair you will meet on blend charts: bubble point is the saturation point where the first bubble of vapor forms in liquid, and dew point is the saturation point where the first drop of liquid forms in vapor. For a pure refrigerant they are the same line. For a blend with glide they split into two columns. Field rule for later modules: subcooling uses the bubble point column, superheat uses the dew point column. For R-410A the two are so close you can ignore the difference.

R-410A deep dive

R-410A is the refrigerant in the overwhelming majority of systems Island Breeze services today, so it gets the deep treatment.

What it is. R-410A is a blend: 50 percent R-32 and 50 percent R-125 by weight. Two different molecules in one bottle.

Why it behaves like a single fluid. Most blends fractionate, meaning the components boil at different rates so the mixture's makeup shifts as it boils, creating glide. R-410A's two components happen to cooperate so closely that its boiling and condensing lines are nearly identical. The technical term is near-azeotropic (an azeotrope is a blend that behaves exactly like a pure compound). Practical result: one PT line works, glide is negligible, and field practice treats R-410A like a pure fluid. This is a property of R-410A specifically, not of blends in general. Do not carry that habit to other blends.

Pressures versus old R-22. R-22 at a 40 F coil runs about 68 psig; R-410A runs 118. R-22 condensing at 115 F runs around 243 psig; R-410A runs 390. R-410A operates at roughly 50 to 60 percent higher pressure across the board. That is why R-410A demanded a whole new generation of compressors, gauges, hoses, and recovery machines rated for the higher pressures, and why you never connect R-22 era equipment to an R-410A system. Its critical temperature (the temperature above which the refrigerant cannot condense no matter the pressure) is about 160 F, with a critical pressure near 696 psig. Those two numbers explain hot-climate behavior: when outdoor air pushes condensing temperatures into the 120s and 130s, R-410A is operating uncomfortably close to its ceiling and efficiency falls off.

Why it is being phased down. R-410A contains no chlorine, so it is completely innocent in the ozone story. Its problem is GWP: at 1,924 (or 2,088 by the older accounting) it is a potent greenhouse gas. Under the AIM Act, the federal law that phases down HFC production, new residential equipment manufactured after January 1, 2025 cannot use it. Critical fact techs get wrong: the phase-down applies to NEWLY MANUFACTURED equipment, not to service. R-410A remains legal to produce for service use, legal to install in existing systems, and will be serviced for decades. You are not breaking any rule by recharging an R-410A system in 2030. You are breaking rules if you vent it, and you are creating a disaster if you put anything else in an R-410A system.

Oil: R-410A runs POE oil, covered below.

Refrigerant families and history: the ozone story, then the GWP story

The refrigerant in the cylinder has changed three times in living memory, and each change makes sense once you know the two environmental problems behind it.

CFCs: the originals. Chlorofluorocarbons, molecules built from chlorine, fluorine, and carbon. R-12 was the king: stable, non-toxic, non-flammable, cheap, and it cooled everything from car AC to refrigerators from the 1930s onward. The fatal flaw took fifty years to discover: CFCs are so stable they drift intact up to the stratosphere, where ultraviolet light cracks the chlorine off, and each freed chlorine atom catalytically destroys ozone molecules, on the order of one hundred thousand ozone molecules per chlorine atom. The ozone layer is the shield that blocks hard ultraviolet radiation. The Montreal Protocol, the 1987 international treaty on ozone-depleting substances, ended CFC production in the United States as of January 1, 1996.

HCFCs: the bridge. Hydrochlorofluorocarbons add hydrogen to the molecule, which makes it less stable, so most of it breaks down before reaching the stratosphere. Less chlorine delivered means less ozone destroyed, but not zero. R-22 was the residential AC workhorse for decades. Because HCFCs still carry chlorine, they were always a bridge: United States production of new R-22 ended in January 2020. Systems running R-22 survive on reclaimed supply only, and finding R-22 on a job is a flag that the equipment predates roughly 2010.

HFCs: the ozone fix. Hydrofluorocarbons contain no chlorine at all. Zero ozone depletion potential. R-134a took over automotive, and R-410A took over residential AC starting in the 2000s. Problem solved? The ozone problem, yes. But HFCs are strong greenhouse gases, and once refrigerants were scored by GWP, R-410A's number put a target on it. The Kigali Amendment to the Montreal Protocol and the AIM Act in the United States now phase HFC production down.

HFOs and the low-GWP era. Hydrofluoroolefins are fluorine-based molecules with a weak double bond that makes them fall apart in the lower atmosphere within days, so they trap almost no heat. R-1234yf is the flagship HFO. The mainstream residential answers are R-32 (an HFC, but with a much lower GWP of 675, used by Daikin and Goodman) and R-454B (a blend of R-32 and the HFO R-1234yf, GWP 466, used by Trane, RunTru, Carrier, Lennox, and York). The trade-off this generation accepted: mild flammability. That is the A2L story previewed below.

The pattern to remember: R-12 solved cooling and created the ozone problem. R-22 softened the ozone problem. R-410A eliminated the ozone problem and inherited the GWP problem. R-32 and R-454B shrink the GWP problem and introduce a flammability trade-off. Every generation is a compromise, and your career will probably see one more swing.

Refrigerant oils: mineral versus POE, and why moisture is the enemy

Refrigerant circulates with oil in it. The oil's job is to lubricate the compressor, but the refrigerant drags a little oil through the entire circuit, so oil and refrigerant must stay mixed and must return to the compressor. Oil and refrigerant are chosen as a pair.

  • Mineral oil is refined from petroleum. It mixes properly with the old chlorine-bearing refrigerants, so R-12 and R-22 systems ran mineral oil.
  • POE (polyolester) oil is a synthetic oil that mixes properly with HFCs and the new A2Ls. R-410A, R-32, and R-454B all run POE.

The pairing is not optional. HFC refrigerant in mineral oil will not carry the oil around the circuit; it settles out in the coils and the compressor starves. This is one of several reasons "drop-in" refrigerant swaps are a myth.

POE's dark side: it is hygroscopic. Hygroscopic means it actively pulls water vapor out of the air, and POE grabs moisture fast and holds it so tightly a vacuum pump struggles to pull it back out. Moisture inside a refrigeration circuit is poison: water plus refrigerant plus heat brews acid, acid attacks compressor motor windings, and free water can freeze into ice at the metering device and block it. Field discipline that follows directly from this chemistry: keep POE containers sealed until the moment of use, do not leave an opened system sitting open to air, cap line sets, and treat the filter drier (the moisture-absorbing cartridge in the liquid line) plus a deep vacuum as mandatory whenever a system is opened. Module C15 turns this into full procedure; F5's job is to make sure you know WHY the rules exist.

Cylinder basics

  • A resting cylinder containing liquid refrigerant is saturated, so the PT chart predicts its pressure exactly from its temperature. This makes cylinders both your practice tool and your purity check: a cylinder reading far above chart pressure for its temperature contains air or the wrong product.
  • Do not trust paint color. For decades each refrigerant had a signature color (R-22 green, R-410A rose) and techs grabbed bottles by color. The industry guideline changed: new refrigerant cylinders are now light gray-green (call it gray) across the board, with the refrigerant identified by the printed label and markings only. A2L cylinders add a red band or red marking to flag flammable contents, and they use left-hand thread connections so non-A2L equipment does not connect by accident. The only identification that counts is the label. Read it every time.
  • Fill limit for recovery cylinders is 80 percent of capacity, because a liquid-full cylinder that warms up has no vapor space left and hydraulic pressure can rupture it.
  • Never expose a cylinder to temperatures above 125 F and never heat one with a flame.
PHOENIX FIELD NOTE
The 125 F cylinder limit is not a hypothetical here. A closed service van parked in the sun on a 115 F Phoenix afternoon can push interior temperatures past 140 F, and a cylinder is saturated, so its internal pressure climbs the PT curve the whole way up. Run the numbers: an R-410A cylinder at 125 F is sitting at 445 psig before anything has gone wrong. Store cylinders low in the truck, shaded, secured upright, and never in a sealed box that bakes. If a bottle has been riding in a hot truck, let it cool before you trust its pressure reading for anything diagnostic.

A2L preview: what is coming (full module is A31)

You will see the term A2L on new equipment, new cylinders, and new tools, so here is the orientation. Full handling procedures, tooling, sensor systems, and code requirements are Module A31, after you have charging and diagnostic skills to attach them to.

  • A2L is an ASHRAE 34 safety classification: A means lower toxicity, 2L means lower flammability with low burning velocity. A2L refrigerants can ignite, but only from serious ignition sources like open flames, and they burn slowly, at less than about 10 centimeters per second of flame speed. Household items like light switches and static from your hand cannot ignite R-454B.
  • R-454B and R-32 are the two A2Ls you will meet, in new equipment manufactured from 2025 on. A2L equipment is marked: flammability labels, and red-marked service ports.
  • The two non-negotiables you need TODAY, even before A31: never put an A2L refrigerant into a system designed for R-410A (no retrofits, no drop-ins, prohibited and dangerous), and never mix refrigerants in a system or a cylinder, period. Mixing R-454B into R-410A creates oil and pressure problems and contaminates every machine that later touches that charge.
  • A2L work requires A2L-rated tools (recovery machine, leak detector, hoses) and supplemental training. You will get both.
IB STANDARD
Island Breeze requires A2L supplemental certification (ESCO Institute or HVAC Excellence) before a tech touches 2025-or-newer A2L equipment, on top of EPA 608. Dispatch enforcement flags uncertified techs on A2L jobs automatically. Until you hold that card, your role on an A2L system is observation only.
PHOENIX FIELD NOTE
Get comfortable now with what hot-climate head pressure looks like on the PT chart, because Phoenix runs the right-hand edge of it. A textbook 95 F day condenses around 115 F, which is 390 psig on R-410A. A 115 F Phoenix afternoon pushes condensing temperatures toward 130 F and beyond, and the gauge climbs past 445 toward 500 psig on a system that is perfectly healthy. A new tech who learned "400 psig is high" from a mild-climate book will misdiagnose half the systems in this valley in July. Saturation math first, judgment second: convert the pressure to a condensing temperature, subtract the outdoor air temperature, and judge the SPLIT, not the raw pressure.

Common Mistakes

  1. Reading the wrong scale ring or menu setting. The R-22 ring on an analog gauge and the R-22 menu choice on a digital manifold will both happily convert your R-410A pressure into a wrong temperature. Every saturation reading starts with confirming the refrigerant setting matches the nameplate.
  2. Treating every blend like a single fluid. R-410A earned that treatment by being near-azeotropic. R-454B has glide, R-407C has serious glide, and blends as a class fractionate when vapor-charged. Learn each refrigerant's behavior; never assume.
  3. Leaving POE oil or an opened system exposed to air. POE is hygroscopic and the moisture it grabs becomes acid and ice inside the circuit. Cap it, seal it, vacuum it. An open line set on a humid day is absorbing the seed of a future compressor failure.
  4. Topping off without identifying the refrigerant. Unknown system history plus abnormal pressures means a possibly mixed or mystery charge. Adding more on top makes it worse and contaminates your gauges, hoses, and recovery cylinder. Nameplate first, label second, and when the charge is suspect: recover it, evacuate, and recharge with virgin refrigerant. Never top off a suspected mix.
  5. Judging raw pressure instead of saturation temperature. 445 psig means nothing by itself. 445 psig as "125 F condensing on a 95 F day" means trouble; the same 445 on a 118 F afternoon is close to normal. Convert first, judge second.

What Is Next

F6 takes the saturation temperatures you can now produce on demand and turns them into the two most important numbers in diagnosis: superheat and subcooling, measured on a live unit.

Module Visuals

1 r410a pt curve
R-410A Pressure-Temperature Curve with Field Anchor Points R-410A Saturation Curve: Pressure vs Temperature Seven anchor values every tech memorizes (psig) 100 200 300 400 0 40 60 80 100 120 Saturation temperature (F) Pressure (psig) Suction side 40 to 50 F Condensing side 95 to 125 F 40 F = 118 45 F = 130 50 F = 142 95 F = 296 105 F = 340 115 F = 390 125 F = 445 Read it both ways: gauge pressure converts to saturation temperature, expected temperature predicts gauge pressure. Liquid and vapor together sit ON this line. Vapor above saturation temp is superheated. Liquid below it is subcooled.
2 refrigerant family timeline
Refrigerant Family Timeline: CFC to HCFC to HFC to Low-GWP A2L Refrigerant History: Two Problems, Four Generations First the industry fixed ozone depletion, now it is shrinking GWP 1930s 1990s 2000s 2025+ CFC R-12 Chlorofluorocarbon Stable, safe, cheap Ozone harm: SEVERE Chlorine destroys ozone GWP: very high US production banned January 1, 1996 Montreal Protocol 1987 HCFC R-22 Adds hydrogen, breaks down before stratosphere Ozone harm: REDUCED Still carries chlorine GWP: high New production ended January 2020 Reclaimed supply only HFC R-410A No chlorine at all 50% R-32 + 50% R-125 Ozone harm: ZERO Ozone problem solved GWP: 1,924 No new equipment after January 1, 2025 Service continues legally Low-GWP A2L R-32 and R-454B R-32: single HFC, GWP 675 R-454B: R-32 + HFO R-1234yf, GWP 466 Ozone harm: ZERO GWP: 675 / 466 Trade-off: mildly flammable (A2L) Full handling: module A31 Ozone depletion severe, then reduced, then zero from HFCs onward GWP ignored at first, now the driving number: 1,924 down to 466 Pattern: each generation fixes the last generation's environmental problem and accepts a new trade-off. Field rule that never changes: the refrigerants are NOT interchangeable. Nameplate and label decide, every time.
3 saturation dome
Saturation Dome: Subcooled Liquid, Saturated Mix, Superheated Vapor The Saturation Dome: Three States, One Map Where the refrigerant is liquid, vapor, or both at once Heat content (enthalpy: total energy stored in the refrigerant) Pressure Critical point: R-410A about 160 F, no condensing above this SUBCOOLED LIQUID 100% liquid below saturation temp leaving the condenser SATURATED MIX liquid + vapor together temperature locked at saturation inside most of both coils THE PT CHART LIVES HERE SUPERHEATED VAPOR 100% vapor above saturation temp leaving the evaporator bubble point first vapor bubble forms dew point last liquid drop boils off one constant pressure Pure fluids and R-410A: bubble and dew sit at one temperature. Blends with glide (R-454B, about 1.5 F): the two points split apart.
4 safety class ladder
ASHRAE 34 Safety Classes: A1 vs A2L vs A3 Flammability Ladder Refrigerant Safety Classes: The Flammability Ladder ASHRAE Standard 34: letter = toxicity, number = flammability A = lower toxicity, B = higher toxicity. 1 = no flame propagation, 2L = lower flammability with slow flame, 2 = flammable, 3 = highly flammable. Every refrigerant in this course is class A: lower toxicity. The number is what changes. A3 HIGHLY FLAMMABLE Example: R-290 (propane) Ignites easily, burns fast. Small charge limits. Niche equipment only. Not residential split systems. A2L MILDLY FLAMMABLE Examples: R-32 (GWP 675), R-454B (GWP 466) Can ignite, but only from serious sources like open flame. Burns slowly: flame speed under about 10 cm per second. New equipment from 2025 on. A2L tools + training required (A31). Cylinders: red marking, left-hand threads. Red service port marks. A1 NO FLAME PROPAGATION Examples: R-410A (GWP 1,924), R-22, R-12 Will not carry a flame. The installed base you service today. Standard tooling. Flammability is not the hazard; pressure is. increasing flammability Never put an A2L refrigerant into a system built for A1. No retrofits. No drop-ins. No mixing. Ever. A2L handling procedures, sensors, and charge limits are covered in full in module A31.

In-Person Practical

Administered by Darrel with a printed rubric. The written quiz below does not replace it.

Module: F5, Refrigerants and the PT Chart Administered by: Darrel Location: Shop bench Time required: 25 to 35 minutes Equipment: R-410A cylinder with liquid (rested at room temperature), analog manifold gauge set with labeled temperature rings, digital manifold or wireless probe with app, laminated paper R-410A PT chart, infrared or clamp thermometer, blank drill sheet, pen

Prerequisite: Tech has passed the F5 quiz (or test-out) before attempting the practical.

Safety baseline (observed throughout, automatic stop on violation): safety glasses on whenever hoses are connected or disconnected, cylinder secured upright, valves opened slowly, no cylinder heating of any kind.

Evaluator Checklist

StepWhat evaluator watches forPass criteriaResult
1. Refrigerant identificationTech checks the cylinder label and markings, not paint color, and states the refrigerant before touching gaugesVerbally identifies R-410A from the label without promptingPass / Fail
2. Prediction before connectionTech measures cylinder shell temperature, then uses the paper PT chart to predict cylinder pressure BEFORE connectingWritten prediction within 5 psig of chart value for measured temperaturePass / Fail
3. Connect and verifyHose connection, slow valve opening, gauge reading compared to predictionSafe connection, reading confirms prediction, tech explains any small difference (temperature settling)Pass / Fail
4. Paper chart drills, pressure to temperatureEvaluator calls 4 pressures from the anchor set; tech finds saturation temperature on the paper chart4 of 4 correct within 1 chart row, each inside 15 secondsPass / Fail
5. Paper chart drills, temperature to pressureEvaluator calls 3 temperatures; tech finds pressure on the paper chart3 of 3 correct within 1 chart row, each inside 15 secondsPass / Fail
6. Gauge dial readingEvaluator points at the analog gauge; tech reads saturation temperature off the correct ring and names which ring was usedReads the R-410A ring correctly and explains why the other rings give different answersPass / Fail
7. Wrong-ring trapEvaluator asks what the R-22 ring shows at the current needle position and why it differsTech reads the R-22 ring, identifies it as the PT chart for a different refrigerant, and states the field consequence of using itPass / Fail
8. Digital probe readingTech connects or uses the digital probe and appSelects R-410A in the app BEFORE trusting the displayed saturation temperature, reading agrees with dial and chartPass / Fail
9. Memory anchorsWith chart and tools face down, evaluator calls 3 anchor values from: 40/118, 45/130, 50/142, 95/296, 105/340, 115/390, 125/4453 of 3 correct from memory, within 5 psig or 2 FPass / Fail
10. Refrigerant family identificationEvaluator names 5 refrigerants (per script below); tech states the family of each5 of 5 correct familiesPass / Fail
11. Safety class statementTech states the ASHRAE safety class of R-410A and R-454B and what each class meansA1 non-flammable vs A2L mildly flammable, with the letter and number decoded correctlyPass / Fail
12. Disconnect and stowHoses disconnected safely, cylinder valve closed, cylinder stowed correctlyValve closed first, cylinder secured upright, tech states the hot truck storage rule and the 125 F cylinder limitPass / Fail

Overall pass requirement: all 12 steps passed. Any failed step may be re-attempted once during the same session after coaching. Two failures on the same step ends the session; tech re-studies and reschedules after 48 hours.

Evaluator Script (Darrel)

Setup: cylinder rested at shop temperature at least 2 hours. Have the drill sheet ready. Keep your own PT chart in hand for scoring.

  1. "Before anything else: what is in this bottle, and how do you know?" (Step 1. Listening for: label and markings, never paint color.)
  2. "Measure the bottle temperature, then write down what pressure it should be sitting at before you hook up. Show me where the chart says so." (Step 2.)
  3. "Connect and check yourself." (Step 3. Watch glasses, slow valve, hose habits.)
  4. Paper chart, pressure to temperature, call these four one at a time: "130 psig." (45 F) "390 psig." (115 F) "118 psig." (40 F) "340 psig." (105 F) (Step 4.)
  5. Paper chart, temperature to pressure, call these three: "50 degrees." (142 psig) "95 degrees." (296 psig) "125 degrees." (445 psig) (Step 5.)
  6. "Now off the dial: what is the saturation temperature right now, and which ring did you use?" (Step 6.)
  7. "Without moving the needle, what does the R-22 ring say, and what would happen to a tech who used it on this bottle?" (Step 7.)
  8. "Now show me on digital. Talk me through your first move in the app." (Step 8. First move must be refrigerant selection.)
  9. "Charts down, tools down. From memory:" call any three anchors, for example "45 degrees is what pressure?" (130) "What temperature is 390?" (115 F) "40 degrees is what pressure?" (118) (Step 9.)
  10. "Family round. Tell me the family for each: R-12." (CFC) "R-22." (HCFC) "R-410A." (HFC blend) "R-32." (HFC, low GWP, A2L era) "R-454B." (HFC/HFO blend, A2L era) (Step 10.)
  11. "Safety classes: R-410A versus R-454B. Decode the letters and numbers for me." (Step 11. A means lower toxicity; 1 means no flame propagation; 2L means mildly flammable with slow flame speed.)
  12. "Wrap it up: disconnect, stow the bottle, and tell me the two rules about cylinders and heat." (Step 12. Listening for: never above 125 F, never store baking in a closed truck, secured upright.)

Coaching notes for the evaluator: if the tech stalls on a drill, let the full 15 seconds run before helping. If they read a wrong ring or skip refrigerant selection on digital, do not correct immediately; let them carry the wrong number one more step so they feel how confidently wrong it is, then coach. Score the re-attempt fresh.

Sign-Off

FieldEntry
Technician name
Technician signature
Evaluator nameDarrel
Evaluator signature
Date
Attempt number1 / 2
Steps passed (of 12)
Re-attempted steps, if any
ResultPASS / RETRAIN
Notes

A PASS here completes module F5. Record the result in the training tracker the same day. F6 (Superheat and Subcooling) unlocks on completion.

Module Quiz (20 questions)

Pass mark is 80 percent. You get one retake; a second miss locks the quiz for 48 hours while you re-study.